Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
DDRH-120-12 is the 12V output model of this series: rated current 8.4A, rated power 100.8W, typical efficiency 88%.
DDRH-120 series is a 250 ~ 1500Vdc high reliable ultra-high input DIN rail type DC-DC converter which can supply stable working voltage for the load. It is suitable to be mounted on TS-35/7.5 or 15 rails. Main features are as following: easy to install DIN rail type, narrow width(63mm) in slim design, -40~+80° C wide range operating temperature, 4KVac high isolation voltage, operation at 5000m altitude, high efficiency, low ripple & noise, complete protections and so on. DDRH-120 is compliant with UL1741 and BS EN/EN61000-6-2 standard regarding immunity for industrial environments. It is suitable for industrial automation, surveillance, telecommunication and can be widely deployed in the applications of new energy generation such as solar power, and windmill power generation, for instances, photovoltaic power systems, high voltage inverting , DC bus centralized application, ESS, charging pile, railway and so forth.
Features
- 250~ 1500Vdc 6:1 ultra-wide input range
- Withstand 1700Vdc surge input for 10 seconds
- 63mm slim width
- 4KVac I/O high isolation(Reinforced isolation)
- Protections: Short circuit / Overload / Over voltage / Over temperature DC input under voltage / DC input reverse polarity
- Fanless design, cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- -40~+80°C ultra-wide operating temperature (>+50°C derating)
- Over voltage categoryⅡ
- Operating altitude up to 5000 meters
- DC OK relay contact
- DC output voltage adjustable(12~15V, 24~29V, 30~36V, 48~58V)
- Conformal coating
- 3 years warranty
Specifications
OUTPUT
- DC VOLTAGE
- 12V
- RATED CURRENT
- 8.4A
- CURRENT RANGE
- 0 ~ 8.4A
- RATED POWER
- 100.8W
- RIPPLE & NOISE (max.)Note.2
- 120mVp-p
- VOLTAGE ADJ. RANGE
- 12 ~ 15V
- VOLTAGE TOLERANCENote.3
- ±1.5%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±1.5%
- EXTERNAL CAPACITANCE LOAD (Max.)
- 4000μF
INPUT
- VOLTAGE RANGENote.4
- 250 ~ 1500Vdc
- EFFICIENCY (Typ.) 300Vdc
- 88%
- EFFICIENCY (Typ.) 800Vdc
- 87%
- EFFICIENCY (Typ.) 1500Vdc
- 84%
- INRUSH CURRENT (max.)
- COLD START 300A /1500Vdc 200A/800Vdc 70A/250Vdc
- EXTERNAL INPUT FUSE
- 4A/1500VDC, required(Please refer to page 4 for more details)
PROTECTION
- OVERLOAD
- 105 ~ 135% rated output power Protection type : Hiccup mode when output voltage<55%, recovers automatically after condition is removed; Constant current limiting, recovers automatically after fault condition is removed within 55% ~ 100% rated output voltage
- OVER VOLTAGE
- 16.5 ~ 21V Protection type : Hiccup mode, recovers automatically after fault condition is removed
- OVER TEMPERATURE
- Protection type : Hiccup mode, recovers automatically after fault condition is removed
- DC INPUT REVERSE POLARITY
- By internal Bridge Diode, no damage, recovers automatically after fault condition removed
- DC INPUT UNDER VOLTAGE LOCKOUT
- Under voltage protection range:200 ~ 230Vdc , Under voltage release range:230 ~ 245Vdc
FUNCTION
- DC OK SIGNAL
- Relay contact rating(max.) : 30V / 1A resistive
ENVIRONMENT
- WORKING TEMP.
- -40 ~ +80℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +80℃, 10 ~ 95% RH non-condensing
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
- OPERATING ALTITUDENote.5
- 5000m
- OVER VOLTAGE CATEGORY
- OVCⅡ2000m; According to EN62109-1
SAFETY & EMC
- SAFETY STANDARDS
- UL1741, CSA C22.2 No.107.1-16 , IEC62109-1, BS EN/EN62109-1, EAC TP TC 004 approved
- WITHSTAND VOLTAGE
- I/P-O/P:4KVAC I/P-FG :3.75KVAC O/P-FG :2KVAC O/P-DC OK:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, 100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
-
Parameter Standard Test Level Conducted BS EN/EN55032(CISPR32) Class A Radiated BS EN/EN55032(CISPR32) Class A - EMC IMMUNITY
-
BS EN/EN55035, BS EN/EN61000-6-2
Parameter Standard Test Level ESD BS EN/EN61000-4-2 Level 3, 8KV air; Level 2, 4KV contact, criteria A Radiated Susceptibility BS EN/EN61000-4-3 Level 3, 10V, criteria A EFT/Burest BS EN/EN61000-4-4 Level 3, 2KV, criteria A Surge BS EN/EN61000-4-5 Level 4, 2KV/Vin+ ~ Vin-, 4KV/Vin ~ FG, criteria A Conducted BS EN/EN61000-4-6 Level 3, 10V, criteria A Magnetic Field BS EN/EN61000-4-8 Level 4, 30A, criteria A
OTHERS
- MTBF
- 257.2 Khrs min. MIL-HDBK-217F (25℃); 1596.3 Khrs min. Telcordia TR/SR-332 (Bellcore) (25℃)
- DIMENSION
- 63*125.2*115mm (W*H*D)
- PACKING
- 0.845Kg; 12pcs/12.6Kg/1.02CUFT
Test conditions and notes7
- 1. All parameters NOT specially mentioned are measured at 800Vdc input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. Derating may be needed under low input voltage. Please check the derating curve for more details.
- 5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- 6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- 7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
Technical drawings
Typical applications
- Photovoltaic power generation
- Renewable energy system
- High voltage frequency conversion
- Industrial control system
- Semiconductor fabrication equipment
- Electro-mechanical apparatus
- DC bus centralized application
- Energy storage system(ESS)
- Charging pile
- Third rail
Downloads
Datasheet1
FAQ
Can the DDRH-120-12 power a 12V industrial control panel drawing around 8A?
Yes, the DDRH-120-12 delivers up to 8.4A at 12V (100.8W), making it suitable for 12V control panel loads up to that current. It mounts on a DIN rail and operates across a 250–1500VDC input range, which suits systems fed from medium-voltage DC bus architectures.
Is the DDRH-120-12 suitable for use in DC microgrid or energy storage systems?
Yes. The DDRH-120-12 accepts a 250–1500VDC input, making it well suited to battery-based DC microgrids and energy storage bus applications where bus voltage may vary widely. An input under-voltage lockout (200–230VDC) protects against a sagging bus, and the output is adjustable from 12V to 15V to accommodate downstream equipment requirements.
Can I use this converter to supply 12V instrumentation in a solar or wind power cabinet?
The DDRH-120-12 is designed for high-voltage DC input environments such as solar string and wind turbine DC buses, accepting 250–1500VDC. It provides a regulated 12V/8.4A output for instrumentation, PLCs, or HMIs mounted in the same cabinet.
What temperature range can the DDRH-120-12 operate in?
The DDRH-120-12 is rated for -40°C to +80°C operation, with output derating at higher ambient temperatures (see the derating curve). This wide range makes it suitable for outdoor cabinets or industrial environments subject to cold-weather extremes without additional heating.
How wide is the DDRH-120-12, and will it fit in a standard DIN rail enclosure?
The DDRH-120-12 is 63mm wide — a slim DIN rail form factor. Its full dimensions are 63 × 125.2 × 115 mm and it weighs 0.845 kg; it mounts on TS35/7.5 or TS35/15 DIN rail.
What output voltage models are available in the DDRH-120 series?
The DDRH-120 series includes four output voltage options: 12V/8.4A (DDRH-120-12, 100.8W), 24V/5A (DDRH-120-24, 120W), 32V/3.75A (DDRH-120-32, 120W), and 48V/2.5A (DDRH-120-48, 120W). All share the same 63mm-wide DIN rail housing and 250–1500VDC input range.
Can the output voltage of the DDRH-120-12 be adjusted above 12V?
Yes, the output voltage is adjustable from 12V up to 15V via the trim function. This allows fine-tuning to match the forward voltage requirements of downstream 12V loads or to compensate for cable drop.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.